SAI3880D发电机保护测控装置加工 欢迎来电洽谈
2.2.4 precision of various components
Current component: <5%
Voltage components: <5%
Time element: 0s-1s, the error is not more than 40ms;
1s above, the error is not more than < + 2.5%;
Frequency deviation: <0.02Hz
2.2.5 the entire set of action time (including the inherent time of the relay)
Time of motion of a fast moving segment:
1.2 times the value of the entire set of measurement, not more than 50ms
2.2.6 transient transcendence
No more than 5%
2.2.7 og measurement loop accuracy
Measurement and control device for installing special measurement sub module:
Current, voltage: 0.2
Power and electric degree: 0.5
2.3 insulation performance
2.3.1 insulation resistance
Device for charged and uncharged part and a casing and electrical contact of the circuit between the open circuit voltage of 500V megohm meter measuring the insulation resistance value, normal test atmospheric conditions, the circuits of each class of insulation resistance should not be less than 100m ohm.
2.3.2 medium strengthUnder normal test conditions, the device can withstand the frequency of 50Hz, voltage 2000V lasted 1 minutes of power frequency voltage withstand test without breakdown flashover and component damage. During the test, the other circuit is connected to the ground with the other circuit when the voltage is applied.
device overview
SAI3880D series digital generator protection device with high performance chip supports universal hardware platform, easy to maintain; the Ethernet communication, high-speed data transmission and reliable. Complete localization of Chinese display technology, simple operation.
Based on waterproof, dust, anti vibration design, can be run in a variety of field conditions.
Suitable for capacity of 50MW and below the fire and hydro generator protection.
1.2 main features of the device
An Motorola 32 bit microcontroller technology, the stability and speed of products is guaranteed
The protection. The 14 bit a / D converter, optional measurement module dedicated to the A / D conversion accuracy is up to 24 bits and the measurement indicators easily reach
The purpose of configuration with high capacity RAM and Flash Memory, can record 8 to 50 recorded reports, record the number of events is not less than 1000
An independent tuning of 32 sets of protection setting value, safe and convenient switch
In high precision clock chip, and equipped with GPS hardware circuit for the whole time, system clock synchronization
It is equipped with high speed Ethernet communication interface, and the integration of IEC870-5-103 standard communication protocol
In the electrical design with the machine, no adjustable device
In high grade, quality assurance component selection
An excellent anti-interference performance, panel or installed in the switch cabinet without other anti-jamming module
The purpose of self diagnosis function perfect
The chassis design of waterproof and dustproof and anti vibration.
The purpose of debugging conceptual design
2.2 Main technical performance
Precise working range of 2.2.1 sampling circuit (10% error)
Voltage: 0.4 V ~ 120V
Current: 0.08In20In
2.2.2 contact capacity
Signal circuit contact current carrying capacity 400VA
Signal circuit contact fault arc capacity 60VA
2.2.3 tripping current
Breaker trip current 0.5A~4A (order indication)
The circuit breaker closing current 0.5A~4A (the order stated)
2.2.4 precision of various components
Current component: <5%
Voltage components: <5%
Time element: 0s-1s, the error is not more than 40ms;
1s above, the error is not more than < + 2.5%;
Frequency deviation: <0.02Hz
1.3 function configurationFunction configuration of SAI3880D digital generator differential protection deviceDifferential quick break, ratio brake differential, CT disconnection locking differential, CT disconnection alarm, stator overvoltage protection, stator ground fault protection, overload alarm, anti time overcurrent protectionFunction configuration of backup protection device for SAI3881D digital generatorTransverse differential protection, loss of excitation protection, rotor one point grounding protection, rotor two points grounding protection composite voltage over current protection, inverse time negative sequence overcurrent protection, Pt disconnection alarm, non electricity protection (generator water shutoff, and the generator thermal, generator excitation accident, main steam valve closed),
3.10 stator overvoltage protection
For generator, in particular to a hydro generator, after load rejection due to the speed control of speed control system can not keep up, is easy to appear the stator voltage exceeds the allowed range of over voltage phenomena; at this point to be equipped with over voltage protection, protection from the generator terminal voltage when any phase of more than setting value by setting the delay action to stop.
3.11 stator ground protection
Generator stator grounding protection can for the generator neutral point ungrounded or via arc suppression coil grounding grounding, protection from the generator end opening of the delta winding voltage when open delta windings voltage greater than setting value by setting the exit delay.